Voltage: 120 V, 50/60 Hz (igniter, motor) 24 V (18-30 VAC) 50/60 Hz (gas valve and air proving switch)
Current Draw (run): 0.2 amps (control only)
Main Valve Rating: 2.0 amps
Motor Relay Rating: 7.4 amps (120 V)
Igniter Relay Rating: 1.0 amp (120 V)
Minimum Flame Current Required: 1.0 µA
Flame Failure Response Time: 0.8 seconds (maximum)
Heat Anticipator Setting: 0.2 amps + gas valve current draw (control is not polarity sensitive)